Mitsubishi Electric MELSEC iQ-F Series CVE-2025-7405: Brief Summary of Critical Missing Authentication Vulnerability

A brief summary of CVE-2025-7405, a missing authentication vulnerability in Mitsubishi Electric MELSEC iQ-F Series CPU modules. Over Modbus TCP, the flaw gives unauthenticated remote users access to device values and program control. Covers affected versions, technical details, and the vendor's security history.

CVE Analysis

11 min read

ZeroPath CVE Analysis
ZeroPath CVE Analysis

2025-08-31

Mitsubishi Electric MELSEC iQ-F Series CVE-2025-7405: Brief Summary of Critical Missing Authentication Vulnerability
Experimental AI-Generated Content

This CVE analysis is an experimental publication that is completely AI-generated. The content may contain errors or inaccuracies and is subject to change as more information becomes available. We are continuously refining our process.

If you have feedback, questions, or notice any errors, please reach out to us.

[email protected]

Introduction

Mitsubishi Electric MELSEC iQ-F Series controllers have no authentication on Modbus TCP. Production lines, water treatment plants, and food manufacturing facilities that use them are open to remote manipulation. Without credentials, an attacker can read or change device values and stop industrial programs, which directly affects operational continuity and safety.

About Mitsubishi Electric and MELSEC iQ-F: Mitsubishi Electric is a global leader in industrial automation, and its MELSEC product line runs in thousands of manufacturing, energy, and infrastructure sites worldwide. The iQ-F Series is one of its core programmable logic controller (PLC) families. It is known for its flexibility and is built into critical operations across many sectors.

Technical information

CVE-2025-7405 comes from the Modbus TCP implementation on MELSEC iQ-F Series CPU modules, which has no authentication. Modbus TCP is a widely used industrial protocol, and on these devices it requires no authentication or authorization for critical functions. Any remote system that can reach the controller's Modbus TCP ports (typically 502 or 503) can:

  • Read device registers (disclosing process values, configuration, and operational data)
  • Write to device registers (altering process parameters, manipulating logic, or causing unsafe states)
  • Stop control programs (causing downtime or process interruption)

The vulnerability is classified as CWE-306 (Missing Authentication for Critical Function). The device does not check the identity or permissions of the remote party, so any Modbus TCP client can issue commands. No code snippets or specific PoC details are publicly available. An attacker needs only network access and knowledge of the Modbus protocol.

Affected systems and versions

The following MELSEC iQ-F Series CPU modules are affected:

  • FX5U Series:

    • FX5U-32MT/ES, FX5U-32MT/DS, FX5U-32MR/ES, FX5U-32MR/DS
    • FX5U-64MT/ES, FX5U-64MT/DS, FX5U-64MR/ES, FX5U-64MR/DS
    • FX5U-80MT/ES, FX5U-80MT/DS, FX5U-80MR/ES, FX5U-80MR/DS
    • Affected firmware: Version 1.060 and later
  • FX5UC Series:

    • FX5UC-32MT/DSS, FX5UC-32MT/DS, FX5UC-64MT/DSS, FX5UC-64MT/DS
    • FX5UC-96MT/DSS, FX5UC-96MT/DS, FX5UC-32MT/DSS-TS, FX5UC-32MT/DS-TS
    • Affected firmware: Version 1.060 and later
  • FX5UJ Series:

    • FX5UJ-24MT/ES, FX5UJ-24MR/ES, FX5UJ-40MT/ES, FX5UJ-40MR/ES
    • FX5UJ-60MT/ES, FX5UJ-60MR/ES, FX5UJ-60MT/ESS, FX5UJ-60MR/ESS
    • FX5UJ-24MT/ES-A, FX5UJ-40MT/ES-A, FX5UJ-60MT/ES-A
    • All firmware versions
  • FX5S Series:

    • FX5S-30MT/ES, FX5S-30MR/ES, FX5S-40MT/ES, FX5S-40MR/ES
    • FX5S-60MT/ES, FX5S-60MR/ES, FX5S-80MT/ES, FX5S-80MR/ES
    • All firmware versions

No patch is planned for most affected models. If Modbus TCP is enabled and reachable, the device is vulnerable regardless of configuration.

Vendor security history

Mitsubishi Electric's security record on the MELSEC product line includes:

  • Earlier authentication bypass and protocol parsing vulnerabilities (see CISA and vendor advisories)
  • A pattern of relying on network-level mitigations rather than firmware patches for OT vulnerabilities
  • A formal PSIRT, established in 2019, and CVE Numbering Authority status since 2020
  • Patch response that varies by product and vulnerability. For CVE-2025-7405, no firmware fix is planned for most models.